Show full item recordAbstract
The goal of the study project is to assess the thermal comfort in the Mechanical
Lecture Room (MLR) at Faculty of Engineering, University of Ruhuna in order to find
the comfortable zone in that air-conditioned room. The subject room with
dimensions of 14.66m x 5.10m x 5.13m and set up with two 36000Btu/h Split Type
air conditioners were tested. The room air temperature varied from 18.5 Celsius to
24.6 Celsius, when both A/C machines were operating at 17 Celsius. The length of
the MLR was divided into 12 parts, while the width was divided into 6 equal parts.
The Temperature values were taken by using 10 J-type thermos couples. The
findings of this study can be used to build and control air-conditioning systems for
the identification of a room's comfort zone in relation to the size of the space and
where the air conditioner is positioned.